표 3. | Table 3. S2 EMP 발생기에 노출된 PLC 동작상태 | PLC operation characteristics in case of S2 EMP generator exposure.

Power[kV/m] / distance[m] LED flicker circuit Charge/discharge circuit RS485 cable induced voltage [V]
15 / 20 Normal Normal 15.2
20 / 15 Normal Normal 19.2
30 / 10 Normal After malfunction, automatic return (Temporary upset) 23.4
60 / 5 Normal After malfunction, no automatic return (Permanent upset) 58.3